Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04360
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/19/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/19/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04360 1.Provide total load on service, existing plus new(this TI) show how existing load obtained. 2. Existing AC-7 shows a 15 kva transformer on power plan, please explain. Ray T Majuta Electrical Pln EX PDSD, C of Tucson 7/19/2012 Ray.Majuta@tucsonaz.gov |
| 07/19/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/19/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 07/19/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/19/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Only one trap may be permitted on a trap arm. Refreence: section 1001.1, UPC 2006. |
| 07/23/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 07/23/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/23/2012 | RONALD BROWN | ADA | REVIEW | Passed | |
| 07/23/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |