Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04356
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the titles for the plumbing plans on sheets PD1.1 and PD 1.2 2. Clarify the size of the trap arm called out in keynote 2 on sheet P1.0. Reference: Section 103.2.3, UPC 2006. 3. Appliances (e.g. soda machine, coffee brewer, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006. 4. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006. 5. Two-compartment sink #24 is shown as being indirectly wasted; what is the purpose of this sink? Reference: Section 801.2, UPC 2006. 6. Provide the capacity of the existing gravity grease interceptor and show that it will not be overloaded with the new fixtures being added Reference: Section 1014.3.6.1, UPC 2006. 7. Provide a sediment trap ("dirt leg") for the water heater, WH-1. Reference: Section 1212.7, UPC 2006. 8. Revise the size of the natural gas pipe serving appliance #12 (hot plate). A load of 260 CFH at 60 feet requires a 1-1/4" pipe per Section 1217.1, UPC 2006. |
| 08/09/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/09/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural details to show how the new Type I hood is to be connected to the building structure. Reference: Section 302.1, IMC 2006. 2. The roof plan on sheet A3.0 shows an existing 4'-6"-tall metal screen adjacent to the proposed location for exhaust fan EF-2. Show how the termination of the fan will comply with Section 506.5.5, IMC 2006. 3. Verify that the construction of the existing partition that will be located next to hood H-3 complies with the requirements of Section 507.9, IMC 2006. |
| 08/13/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04356 4811 N Stone Av El Taco Tote 1. Provide a 2006 IECC Budget lighting Report for the Interior. 2. Indicate on plans that receptacles required to be GFCI protected per 2005 210.8(B).2 Ray T Majuta Elect Pln Ck DSD, C of Tuc, 8/13/2012 520-837/4988 |
| 08/16/2012 | FRODRIG2 | WWM | REVIEW | Needs Review |