Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM04343
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/04/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 25: SHEET S1.7; WOOD TRUSS SCHEDULE: THERE ARE NO TRUSS GIRDER DESIGNATIONS IN THE WOOD TRUSS SCHEDULE. THE ROOF AND FLOOR FRAMING PLANS ON SHEETS S2.2, S2.3, AND S2.4 INDICATE TRUSS GIRDERS. PROVIDE THOSE IN THE SCHEDULE. 2. GENERAL: COMMENTS FOR THE RECREATION BUILDING AND MAINTENANCE BUILDING ARE POSTED UNDER THEIR RESPECTIVE ACTIVITY NUMBERS (T12CM04333 AND T12CM04657). |
| 09/12/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed for this building. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Comment not addressed for this building. Provide energy code compliance calculations for the mechanical systems. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. |
| 09/12/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; the civil plans still show a 4" building sewer. [Original comment: Clarify the note on the first floor plumbing plan regarding the "alternate location" for the location of the connection of the building drain and the building sewer. How is the location of the connection of the building drain and the building sewer changing the size of the building sewer from 6" to 4" on the plumbing floor plan but not on the riser drawing? Note that the civil plans show all of the apartment buildings having 4" building sewers. ] 2. Provide sheet P2.3. |
| 09/13/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. THE PLACE A PRESIDIO TRAIL - S12-017/DP12-0061 - CLUBHOUSE (18FU'S) - T12CM04333 - 13-APARTMENT BUILDINGS (3614FU'S) T12CM04334 THRU T12CM04345 & T12CM04347 - MAINTENANCE BUILDING (11FU'S) T12CM04657 2. NEED TO BUILD PUBLIC SEWER/NEED PUBLIC SEWER APPROVAL AND PUBLIC SEWER CONSTRUCTION PERMIT AND HOLD HARMLESS LETTER-NEED TO PERMIT ON-SITE PRIVATE SEWER #PT12S00910 - NEED DEQ REVIEW & APPROVAL TO CONSTRUCT ON-SITE PRIVATE SEWER - NEED COPY OF ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE 3. NEED TO INDICATE SIZE OF WATER METERS ON "WATER SERVICES" TO SERVE BUILDINGS ON PUBLIC WATER PLANS - NOTE: THIRTEEN 2" WATER SERVICES" FOR 13-APARTMENT BUILDINGS AND ONE 1 1/2 "WATER SERVICE" FOR CLUBHOUSE AND ONE 1" " WATER SERVICE" FOR MAINTENANCE BUILDING FOR SEWER CONNECTION FEE CALCULATION |
| 09/13/2012 | TERRY STEVENS | ZONING | REVIEW | Denied | Zoning cannot approve until buliding and the development plan has been approved. |