Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM04337
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The waste stacks serving the automatic clothes washers (P5) shall have a 3" minimum size. Reference: Sections 406.3 and 910.4, IPC 2006. 2. Horizontal branches shall connect to horizontal offsets of vertical stacks a minimum distance of ten times the diameter of the vertical stack downstream of the vertical stack. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/05/2014 | CPIERCE1 | REJECT SHELF | Completed |