Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM04337
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/12/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/19/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the envelope calculations to correlate with the building plans (i.e. the wall and window areas appear to be for only one of the two stories and no doors are included in the list of components). [Previous comments: Comment not addressed for this building. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.] Note: sign the envelope energy calculations. |
| 10/19/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; civil sheets 22 and 23 of 39 still show 4" building sewers but civil sheets 25, 26, and 27 of 39 now show the correct 6" building sewers. [Second comment: Comment not resolved; the civil plans still show a 4" building sewer.] [Original comment: Clarify the note on the first floor plumbing plan regarding the "alternate location" for the location of the connection of the building drain and the building sewer. How is the location of the connection of the building drain and the building sewer changing the size of the building sewer from 6" to 4" on the plumbing floor plan but not on the riser drawing? Note that the civil plans show all of the apartment buildings having 4" building sewers. ] |
| 10/29/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: THE PLACE AT PRESIDIO TRAIL - S12-017/DP12-0061 - CLUBHOUSE (18FU'S) - T12CM04333 - 13- APARTMENT BUILDINGS (3614 FU'S) T12CM04334 THRU T12CM04345 & T12CM04347 - MAINTENACE BUILDING (11FU'S) T12CM04657 2: NEED TO BUILD PUBLIC SEWER/NEED PUBLIC SEWER APPROVAL AND PUBLIC SEWER CONSTRUCTION PERMIT AND HOLD HARMLESS LETTER- NEED TO PERMIT ON SITE PRIVATE SEWER #PT12S00910 - NEED DEQ REVIEW AND APPROVAL TO CONSTRUCT ON SITE PRIVATE SEWER- NEED COPY OF ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE 3: SEWER CONNECTION FEES : THIRTEEN 2" WATER METERS FOR 13-APARMTMENT BUILDING AND ONE 1" WATER METER FOR CLUBHOUSE AND ONE 5/8" WATER METER FOR MAINTENANCE BUILDING |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/06/2012 | SHANAE POWELL | REJECT SHELF | Completed |