Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM04336
Parcel: 134031450

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM04336
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The waste stacks serving the automatic clothes washers (P5) shall have a 3" minimum size. Reference: Sections 406.3 and 910.4, IPC 2006.
2. Horizontal branches shall connect to horizontal offsets of vertical stacks a minimum distance of ten times the diameter of the vertical stack downstream of the vertical stack.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/05/2014 CPIERCE1 REJECT SHELF Completed