Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/18/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
07/18/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
07/18/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
07/18/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/18/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET 2: PROVIDE A DETAIL INDICATING BRACING AT THE TOP OF THE NEW PARTITION WALLS THAT IS CAPABLE OF RESISTING HORIZONTAL LOADS AS REQUIRED BY THE IBC SECTION 1607.13. INCLUDE BRACING SIZE AND SPACING, AND THE CONNECTION OF THE BRACING TO THE TOP OF THE PARTITION WALL AND TO THE EXISTING ROOF STRUCTURE ABOVE. |
07/18/2012 | FRODRIG2 | WWM | REVIEW | Needs Review | |
07/18/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A vent pipe shall not be used as a waste pipe. Reference: Section 311.4, UPC 2006. 2. Provide an upper terminal cleanout for the new sinks. Reference: Section 707.4, UPC 2006. |
07/18/2012 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
07/18/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
07/18/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
07/18/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |