Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM04332
Parcel: 11706081G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04332
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
07/18/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/18/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/18/2012 ROBERT SHERRY WATER REVIEW Approved
07/18/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 2: PROVIDE A DETAIL INDICATING BRACING AT THE TOP OF THE NEW PARTITION WALLS THAT IS CAPABLE OF RESISTING HORIZONTAL LOADS AS REQUIRED BY THE IBC SECTION 1607.13. INCLUDE BRACING SIZE AND SPACING, AND THE CONNECTION OF THE BRACING TO THE TOP OF THE PARTITION WALL AND TO THE EXISTING ROOF STRUCTURE ABOVE.
07/18/2012 FRODRIG2 WWM REVIEW Needs Review
07/18/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A vent pipe shall not be used as a waste pipe. Reference: Section 311.4, UPC 2006.
2. Provide an upper terminal cleanout for the new sinks. Reference: Section 707.4, UPC 2006.
07/18/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
07/18/2012 KEN BROUILLETTE FIRE REVIEW Approved
07/18/2012 ERIC NEWCOMB ADA REVIEW Passed
07/18/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed