Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM04302
Parcel: 11005014C

Address:
2930 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM04302
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; DEMOLITION PLAN: NOTE 10 LISTED IN THE DEMOLITION KEYNOTES IS NOT ON THE PLAN. VERIFY.
2. GENERAL: DEFERRED SUBMITTALS WILL NOT BE REVIEWED UNLESS PREVIOUSLY SUBMITTED TO THE BUILDING OFFICIAL (RON BOOSE) @RON.BOOSE@TUCSONAZ.GOV.
07/17/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/17/2012 LOREN MAKUS ENGINEERING REVIEW Approved
07/18/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond Fire sprinkler permit required for canopy if connected to a fire sprinklered building
07/19/2012 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed