Permit Number: T12CM04250
Parcel: 13415001F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04250
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2012 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
07/18/2012 CPIERCE1 FIRE REVIEW Needs Review
08/01/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/01/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM04250
7750 E Broadway #200

The Mechanical plans show a new exhaust fan, cannot find in electrical plans.
The Plumbing plans show 3 new water heaters,all electrical, WH1- 4.1KW 208v 1P, WH2 and 3 - both 8.3 KW 208v 1P.

Ray T Majuta
Electrical Plan Review
PDSD, C of Tuc
8/01/2012
Ray.Majuta@tucsonaz.gov
08/01/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/02/2012 CPIERCE1 WATER REVIEW Approved