Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04250
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/18/2012 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/18/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 08/01/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/01/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04250 7750 E Broadway #200 The Mechanical plans show a new exhaust fan, cannot find in electrical plans. The Plumbing plans show 3 new water heaters,all electrical, WH1- 4.1KW 208v 1P, WH2 and 3 - both 8.3 KW 208v 1P. Ray T Majuta Electrical Plan Review PDSD, C of Tuc 8/01/2012 Ray.Majuta@tucsonaz.gov |
| 08/01/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/02/2012 | CPIERCE1 | WATER | REVIEW | Approved |