Permit Number: T12CM04250
Parcel: 13415001F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04250
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2012 STEVE SHIELDS ZONING REVIEW Approved
07/16/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
07/16/2012 ERIC NEWCOMB ADA REVIEW Passed
07/16/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS.1; PROJECT CODE CHECK: INDICATE ON THE PLANS (SHEET A.1) WHERE EACH SUITE (A200/D200/B200/C150) IS LOCATED.
2. SHEET A.1; FIRST FLOOR PLAN: DETAIL 4/A2 (THROUGH THE NEW WALL PARTITION) INDICATES THE PARTITION IS SUPPORTED BY METAL STUDS. PROVIDE STRUCTURAL CALCULATIONS FOR THIS SUPPORT, AND INDICATE CONNECTIONS OF THE NEW SUPPORTS TO THE EXISTING STRUCTURE. INCLUDE A STRUCTURAL ANALYSIS OF THE EXISTING STRUCTURE TO SUPPORT THIS ADDITIONAL PARTITION LOAD.
3. SHEET A.1; FIRST FLOOR PLAN: PROVIDE AN ANALYSIS TO INDICATE ONE EXIT FOR CONFERENCE ROOM-1 OR CONFERENCE ROOM-2 IS ADEQUATE WHEN SEPARATED BY THE PARTITION.
4. SHEET A.1; FIRST FLOOR PLAN: IF TWO EXITS ARE REQUIRED FOR THE CONFERENCE ROOMS (COMBINED), THE DOORS MUST BE SEPARATED PER THE IBC SECTION 1015.2.1. VERIFY.
5. SHEET A.1; PLAN 4: SINCE THE MEN'S/WOMEN'S RESTROOMS ARE BEING ALTERED, THEY MUST MEET ACCESSIBILITY STANDARDS OF THE ICC/ANSI. VERIFY.
6. GENERAL: PROVIDE GRAB BARS IN THE RESTROOMS PER ICC/ANSI FIGURES 604.5.1 AND 604.5.2. THIS WILL SATISFY THE 20% MAXIMUM COST ISSUE FOR ACCESSIBILITY.
7. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS.
07/16/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/17/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
07/17/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
07/17/2012 ROBERT SHERRY WATER REVIEW Denied Provide the size of the existing water meter and the reduced pressure backflow assembly.
07/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/18/2012 GERRY KOZIOL WWM REVIEW Approved
07/18/2012 CPIERCE1 FIRE REVIEW Needs Review