Permit Number: T12CM04249
Parcel: 11706072A

Address:
218 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04249
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2012 STEVE SHIELDS ZONING REVIEW Approved
07/16/2012 ERIC NEWCOMB ADA REVIEW Passed
07/16/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T-0; BUILDING/CODE INFORMATION: ACCESSIBILITY REQUIREMENTS MUST MEET ICC/ANSI A117.1-2003, NOT ADAAG. REVISE NOTE.
2. SHEET T-0; BUILDING/CODE INFORMATION: A LEASING OFFICE FALLS UNDER A 'B' OCCUPANCY TYPE PER THE IBC. WHAT IS THE RETAIL PORTION?
3. SHEET T-0; BUILDING/CODE INFORMATION: CLARIFY WHAT IS MEANT BY THE OCCUPANT LOAD AS STATED (16/27).
4. SHEET T-5; DETAIL 14: PROVIDE THE LOCATION OF THE PAPER DISPENSER PER ICC/ANSI A117.1, FIGURE 604.7.
5. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS.
07/16/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/17/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations for the size of the combustion/relief ducts
07/17/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the installed height of the reduced pressure backflow assembly.
07/17/2012 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter 27, Article V, Section 27-76 (a), Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-
07/17/2012 KEN BROUILLETTE FIRE REVIEW Approved
07/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/24/2012 GBONILL1 WWM REVIEW Needs Review
07/24/2012 GBONILL1 ENGINEERING REVIEW Needs Review