Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM04248
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | Approval is conditioned on second fire hydrant available near the site. Fire Sprinklers may be required if second hydrant is not available. DP12-0099 was denied because second fire hydrant was not shown. |
| 07/20/2012 | JASON GREEN | ENGINEERING | REVIEW | Denied | Building plan will be approved after approval of the DP Package (DP12-0099). |
| 07/24/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Where office areas are to recieve 5/8" plywood decking above ceiling, provide signage to the effect that no storage is allowed on this decking. 2. At details aa/A6 and 4/D1, please provide 1 accessible window as per ICC A117.1, Section 904. 3. Detail 1/A6, please indicate a 3'-0" wide dimension for both urinal stalls. END OF REVIEW |
| 07/30/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. SEE SHEET P-2 DETAIL 1. REFERENCE: 707.4 2006 UPC. EXCEPTION ONE. CLEANOUTS MAY BE OMITTED ON A HORIZONTAL DRAIN LINE LESS THAN FIVE FEET IN LENGTH, UNLESS SUCH LINE IS SERVING SINKS OR URINALS. pROVIDE FULL SIZE CLEANOUT FOT P-5 MOP SINK. 2. SEE SHEET P-2 DETAIL ONE. REFERENCE: TABLE 7-5 2006 UPC. MINIMUM SIZE VENT FOR A WATER CLOSET IS TWO INCHES. MINIMUM SIZE VENT FOR A MOP SINK IS TWO INCHES. MINIMUM SIZE VENT FOR A URINAL IS TWO INCHES. 3. SEE SHEET TWO DETAIL ONE. REFERENCE: 908.0 2006 UPC. VERTICAL WET VENTING. SHOW THE DRAIN SIZE BETWEEN THE URINAL AND THE WATER CLOSET ON THE WET VENTED SECTION. |
| 07/30/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006. 2. Revise detail 2/MP1 to eliminate elements that do not apply to the installation of the evaporative coolers on a standing seam metal roof. Reference: Sections 106.3.1 and 302.1, IMC 2006. |
| 07/30/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/03/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/08/2012 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Discount Cab T12CM04248 Building Plan (1st Review) TRANSMITTAL DATE: August 8, 2012 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until the development package has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at |
| 08/20/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. TOTAL TRANSIT- OFFICE MAINTENANCE BUILDING #2 2. CONNECTING TO EXISTING ON-SITE PRIVATE SEWER 3. $4066.00 CREDIT GIVEN FOR REMOVAL OF 3/4 WATER METER AND INSTALLING 1-1/2" WATER METER PER COT DP PACKAGE #11-053 4. NEED ADDRESSSING REVIEW/MICHELENE- 740-6480 TO ADD BUILDING #2 - NEED SITE PLAN SUBMITTAL & NEED TO PAY $75.00 |
| 08/21/2012 | JEFF DRUMM | LANDFILL | REVIEW | Approved | LF ORDINANCE OIL |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/22/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |