Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04207
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 07/13/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations demonstrating adequate ventilation; show the balancing data on the drawing. Reference: Sections 106.3.1 and 403.3, IMC 2006, as amended by the City of Tucson. |
| 07/13/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/13/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/13/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET 7: PROVIDE LATERAL BRACING AT THE TOP OF THE PARTITION WALL TO MEET IBC SECTION 1607.13.INCLUDE BRACE SIZE, SPACING, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE AND THE TOP OF THE WALL. |
| 07/13/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/13/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide equipment data for the proposed water heater. Reference: Section 103.2.3, UPC 2006. 2. Show how the temperature of the hot water supply to the public lavatory is to be controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 3. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy. See also, Section 1109.5.1, IBC 2006. |
| 07/13/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/13/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 08/03/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/09/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |