Permit Number: T12CM04207
Parcel: 10408005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04207
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2012 KEN BROUILLETTE FIRE REVIEW Approved
07/13/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations demonstrating adequate ventilation; show the balancing data on the drawing. Reference: Sections 106.3.1 and 403.3, IMC 2006, as amended by the City of Tucson.
07/13/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/13/2012 ROBERT SHERRY WATER REVIEW Approved
07/13/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 7: PROVIDE LATERAL BRACING AT THE TOP OF THE PARTITION WALL TO MEET IBC SECTION 1607.13.INCLUDE BRACE SIZE, SPACING, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE AND THE TOP OF THE WALL.
07/13/2012 JASON GREEN ENGINEERING REVIEW Approved
07/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide equipment data for the proposed water heater. Reference: Section 103.2.3, UPC 2006.
2. Show how the temperature of the hot water supply to the public lavatory is to be controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
3. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy. See also, Section 1109.5.1, IBC 2006.
07/13/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/13/2012 ERIC NEWCOMB ADA REVIEW Passed
08/03/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
08/09/2012 CPIERCE1 WWM REVIEW Needs Review