| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the gas line between the fryer (FB-1) and the griddle (GR-1) to 1-1/4" to accommodate 186 CFH at a developed length of 125-feet. 2. Provide a specification for the underground gas pipe. |
| 10/02/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Reprint sheet M100 so that it is legible. Reference: Section 106.3.1, IMC 2006. |