Permit Number: T12CM04179
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04179
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved Please provide a letter addressing the four structural calculation items as being structurally sound and signed and sealed by the registrant.
08/13/2012 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
08/13/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/14/2012 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approv-Cond UPC section 1014.3.4.1 "... A gravity grease interceptor complying with IAPMO PS 80, shall not be installed in any part of a building where food is handled...."

Please clarify / justify current location of indicated Schier grease interceptor. While I can accept locaton you must also make sure Pima County Health is ok with this.
08/15/2012 GERRY KOZIOL WWM REVIEW Approved