Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM04166
Parcel: 10406011E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04166
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2013 FRODRIG2 WWM REVIEW Needs Review
08/03/2012 STEVE SHIELDS ZONING REVIEW Approved
08/03/2012 ROBERT SHERRY WATER REVIEW Approved
08/03/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM04166

The water heater is shown in the plumbing sheet as 240 volt 3000 watt load, the electric panel schedule is showing only a 20 amp single phase load with only 1500 watt load ?

Ray T Majuta
8/3/2012
08/03/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide 75 CFM exhaust per water closet
08/03/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE PROJECT INFORMATION ON THE DRAWINGS PER THE IBC SECTION 106 (OCCUPANCY TYPE, OCCUPANT LOAD, PLUMBING FIXTURE REQUIREMENTS, ETC).
2. IF THIS IS AN OFFICE OCCUPANCY TYPE, THE OCCUPANT LOAD WILL BE 30, WHICH WILL REQUIRE TWO ACCESSIBLE RESTROOMS. VERIFY.
3. A HIGH/LOW DRINKING FOUNTAIN (OR SINGLE POINT OF USE WATER DISPENSER) AND A SERVICE SINK ARE REQUIRED PER IBC TABLE 2902.1. VERIFY.
4. SHOW AN ANALYSIS OF EGRESS/EXITING AS REQUIRED BY THE IBC.
5. PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/03/2012 JASON GREEN ENGINEERING REVIEW Approved
08/03/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified water heater cannot limit the water temperature to 110 degrees Farenheit.
2. Provide a cleanout for the water closet.
08/03/2012 MARTIN BROWN FIRE REVIEW Approved
08/03/2012 ERIC NEWCOMB ADA REVIEW Passed
08/03/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved