Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04166
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2013 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 08/03/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/03/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/03/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04166 The water heater is shown in the plumbing sheet as 240 volt 3000 watt load, the electric panel schedule is showing only a 20 amp single phase load with only 1500 watt load ? Ray T Majuta 8/3/2012 |
| 08/03/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide 75 CFM exhaust per water closet |
| 08/03/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE PROJECT INFORMATION ON THE DRAWINGS PER THE IBC SECTION 106 (OCCUPANCY TYPE, OCCUPANT LOAD, PLUMBING FIXTURE REQUIREMENTS, ETC). 2. IF THIS IS AN OFFICE OCCUPANCY TYPE, THE OCCUPANT LOAD WILL BE 30, WHICH WILL REQUIRE TWO ACCESSIBLE RESTROOMS. VERIFY. 3. A HIGH/LOW DRINKING FOUNTAIN (OR SINGLE POINT OF USE WATER DISPENSER) AND A SERVICE SINK ARE REQUIRED PER IBC TABLE 2902.1. VERIFY. 4. SHOW AN ANALYSIS OF EGRESS/EXITING AS REQUIRED BY THE IBC. 5. PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 08/03/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 08/03/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified water heater cannot limit the water temperature to 110 degrees Farenheit. 2. Provide a cleanout for the water closet. |
| 08/03/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/03/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 08/03/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved |