Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM04136
Parcel: 141185240

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM04136
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2012 KEN BROUILLETTE FIRE REVIEW Denied 1. Change the referenced code to the 2006 Edition of the International Fire Code.
2. Remove reference to the "Phoenix" Building Code
3. The fire hydrant and fdc will be required to be located in an island to the west of the island shown for the proposed fire hydrant. The landscaping may need to be changed to provide a 3 foot clearance around the Fire hydrant and FDC.
4. Please note that the fire alarm and fire sprinkler submittals are separate permits. I saw the note for the AST but could not find the deferral note for the fire sprinklers and fire alarm systems.
5. Indicate that emergency egress illumination will be installed and indicate which page shows the location of these devices.
07/19/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. The City of Tucson Design Standards require a minimum actual lettering size on all of the drawing documents of 3/32" for both upper and lower case. Several sheets of your submittal fail to meet this standard. Please revise all below standard lettering sizes on all sheets and resubmit.
2. A structural review could not be conducted because there are no structural foundation and roof framing calculations. Please provide two sets of structural calculations.
3. Please provide additional structural calculations for the following:
a. All roof top mounted HVAC equipment
b. Wall mounted Water Heater support bracket and wall analysis.
c. Suspended mounted electrical transformer
d. Electrical pole concrete foundations
4. If your steel trusses are to be a deferred submittal please submit a letter directly to the building official, Mr. Ron Boose, stating that fact.
SHEET AL2.1
5. Please refer to ther City of Tucson building code as the 2006 IBC not the Phoenix building code.
SHEET A2
6. Provide an interior wall section that shows the "4" minimuim above ceiling" partition and how it complies with the 2006 IBC, Section 1607.13, laterial loading.
SHEET A5.1
7. Please provide a large scale toilet plan showing all accessibility requirements such as dimensioning, fixtures, clearances, accessories and signage.
END OF REVIEW
07/25/2012 ROBERT SHERRY WATER REVIEW Approved
07/26/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
07/26/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the reason for the installation of the reduced pressure principle backflow prevention assembly located in the janitor's room. Reduced pressure principle backflow prevention assemblies intended to protect the public water system are required to be installed in locations accessible to Tucson Water; the civil drawings show the required valve assembly adjacent to the water meter. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
2. Provide backflow protection for the water distribution system from the freeze-proof yard hydrant. Reference: Section 602.3, UPC 2006.
3. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
07/30/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM04136
9398 E Old Vail Rd

All references to the 2005 NEC

1.Sheet E6.4,please shade in Hazardous Areas,and indicate
on this sheet where the seals are to be located per 514.9(A and B) include vertical as well as horizontal bounderies.
2. Describe how Section 514.13 is to be complied with ?
3.Sheet E8.1, Please indicate for contractor to identify panels per 110.15 and 408.3(E).
4. Regarding Transformer T-TK1, 150KVA, where is the location of this on the plans ?
5. Regarding Panels TK1 and TK2, cannot locate them on the electrical sheets, I do see the 400 AMP 3-pole disconnect on Sheet E0.1. Also on Sheet E6.1, the Truck Panel mounting detail is shown for Panels TK1,2 and 3. Do not see Panel TK3 on the one line diagram ?
6. Cannot find the following circuits which are in the panel schedules, TK1 circuits 10,12 and TK2 circuits 4,6,8 and 10

Ray T Majuta
Elect Plan Review
PDSD, city of Tucson
7/31/2012
Ray.Majuta@tucsonaz.gov
07/31/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Blue Bell Creameries - 9398 E. Old Vail Road
T12CM04136
Building Plan (1st Review)

TRANSMITTAL DATE: July 31, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
08/06/2012 PAUL MACHADO ENGINEERING REVIEW Denied Project status will be changed to approved, if applicable, with the dev.pkg. review.
08/08/2012 GERRY KOZIOL WWM REVIEW Denied 1. BLUE BELL CREAMERIES - DISTRIBUTION BRANCH
2. NEED APPROVED WATER PLAN SHOWING SIZE AND LOCATION OF WATER METER OR NEED WATER METER RECEIPT FOR SEWER CONNECTION FEE CALCULATION 1-1/2 DOMESTIC WATER LINE
3. NEED 3RD FLOOR PCRWRD / CHAD AMATEAU REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER 740-6547
4. NEED PCRWRD 1ST FLOOR MANHOLE TAP PERMIT APPROVAL DENISE ELLE 740-6369

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2012 CPIERCE1 OUT TO CUSTOMER Completed