Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2012 MICHAEL ST. PAUL ZONING REVIEW Approved Approval by the Design Review Board is required.
07/12/2012 GERRY KOZIOL WWM REVIEW Approved
07/19/2012 MICHAEL ST. PAUL DRB REVIEW Approved
07/25/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 7-31-12
Activity: T12CM04098
Address: 189 S Avenida Del Semerador
Applicant: Tom Wuelpern

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

FLOOR PLAN:
1. Specify safety glazing in hazardous locations, R308.4. Within 24" of doorways.
2. The walls and soffit of the enclosed space under stairs shall be protected on the enclosed side with ½" gypsum board, R311.2.2.
3. Clarify window sizes and operation type on window schedule for windows: A, B, C, and F.

ELECTRICAL PLAN:
4. Show the location of the panel with a 30"W x 36"D clear working space, E3305.2, E3501.6.2. Plan shows a 36"W x 30"D working space.
5. Clarify conductor sizes for water heater circuit.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review