Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04064
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET D1.1; DEMOLITION KEYNOTES: KEYNOTE 6 WAS NOT FOUND ON THE PLANS. VERIFY. 2. SHEET A2.1; KEYNOTES: THE TITLE FOR THE UPPER KEYNOTES (HEXAGONAL SYMBOL) INDICATES ROOF PLAN KEYNOTES. REVISE TO REFLECTED CEILING KEYNOTES. 3. SHEET A3.1; SECTION KEYNOTES: KEYNOTES 2, 13, 19, 20, AND 21 WERE NOT FOUND ON THE SECTIONS. VERIFY. 4. SHEET S2.1 (FRAMING PLAN); SHEET S4.1 (DETAIL 410): DOES THE EXISTING STEEL BEAM INDICATED IN DETAIL 410 EXTEND THROUGH THE OPEN AREA SHOWN ON THE PLAN? VERIFY. 5. ARCHITECTURAL GENERAL: PROVIDE A PLAN OF THE EXISTING MEZZANINE AND THE MEZZANINE ADDITION. INCLUDE SECTIONS/DETAILS AS REQUIRED. 6. ARCHITECTURAL GENERAL: PROVIDE A DETAIL FOR THE SUPPORT OF THE WATER HEATER ABOVE THE SERVICE SINK. INCLUDE MEMBER SIZES, SPACING, AND ALL PERTINENT CONNECTIONS. 7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 07/26/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006. |
| 07/26/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify keynote #6 on sheet P1.0: is a floor drain really outside of the building? 2. Clarify keynote #9 on sheet P1.0: the specified water heater is not normally installed with a temperature & pressure relief. If a temperature & pressure relief is desired, show how it is to be installed on the installation detail. Reference: Section 103.2.3, UPC 2006. 3. Install the specified water heater in accordance with its listing information. This water heater must not be installed above the level of any of the hot water outlets it serves. Correct detail 201 to correspond to the piping configuration of the specified water heater. Reference: Section 310.4, UPC 2006. |
| 07/26/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/27/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04064 1. The Insta Hot water heater shown in Sheet P-1 is 7.5KW 240 v, the panel schedule shows one 20 CB, also the load is incorrect. Ray T Majuta Elect Pln Review PDSD, C of Tuc 7/27/2012 Ray.Majuta@tucson az.gov |
| 07/30/2012 | TERRY STEVENS | ZONING | REVIEW | Denied | Zoning cannot approve the buliding plan until the development package has been approved. |
| 08/02/2012 | JASON GREEN | ENGINEERING | REVIEW | Denied | Building plan will be stamped approved by the ENG Section after approval of the DP Package DP12-0100. |
| 08/07/2012 | GBONILL1 | WWM | REVIEW | Approved |