Permit Number: T12CM04049
Parcel: 113100990

Address:
2611 N WARREN AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM04049
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2012 JASON GREEN ENGINEERING REVIEW Approved
09/04/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond Prior to installation, submit spec. manuals and all details on generator. Generator shall meet all NFPA 110 and IFC 2006 edition requirements. This approval on T12CM04049 is not an approval of the generator, just the location of the generator on the site. Generator shall be connected to Fire Alarm system per NFPA 72. Fire Alarm Permit will be required. Generator Acceptance test will be required..
09/05/2012 TERRY STEVENS ZONING REVIEW Approved