Review Details: RESUBMITTAL
Permit Number - T12CM04049
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/31/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/04/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | Prior to installation, submit spec. manuals and all details on generator. Generator shall meet all NFPA 110 and IFC 2006 edition requirements. This approval on T12CM04049 is not an approval of the generator, just the location of the generator on the site. Generator shall be connected to Fire Alarm system per NFPA 72. Fire Alarm Permit will be required. Generator Acceptance test will be required.. |
| 09/05/2012 | TERRY STEVENS | ZONING | REVIEW | Approved |