Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM04049
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | Prior to installation, submit spec. manuals and all details on generator. Generator shall meet all NFPA 110 and IFC 2006 edition requirements. This approval on T12CM04049 is not an approval of the generator, just the location of the generator on the site. |
| 07/20/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/20/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Need another sheet A-1. 2. Please provide structural specifications for the concrete pad and a section showing sub-surface preparation and specifications. 3. Please provide fence details, elevations and structural calculations. END OF REVIEW |
| 07/27/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/30/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM04049 2611 N Warren Catalina Care Center 1. Provide Fault Current Calculations. 2. Sheet A-1 shows Panels EQ1,CR1 and LS1 behind and up next to ATS1,2 and 3. How are these to be installed and mounted being next to each other? 3. NEC 2005, 700.27, Emergency systems overcurrent devices shall be selectively coordinated with all supply side overcurrent protective devices, please provide an analysis for this. Ray T Majuta Elect Plan Review PDSD, C of Tucson 7/30/2012 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/06/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |