Permit Number: T12CM04045
Parcel: 12703559C

Address:
5515 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04045
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.0: THIS SHEET INDICATES "FUTURE MEDICAL OFFICES". WILL THERE BE NO DEMOLITION TO THE EXISTING FLOOR PLAN? VERIFY.
2. SHEET A0.0; CODE ANALYSIS: PROVIDE THE OCCUPANCY LOAD, PLUMBING FIXTURE REQUIREMENTS AND PROVIDED, AND THE EGRESS WIDTH REQUIREMENTS AND PROVIDED ON THIS SHEET.
3. SHEET A-2.2; FLOOR PLAN: PROVIDE A NOTE ON THE PLAN THAT REFERENCES APPLICABLE SHEET NUMBERS FOR THE MILLWORK ELEVATIONS (DENOTED BY A DIAMOND SYMBOL).
4. SHEET A-2.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE MILLWORK ELEVATION REFERENCES AND MISCELLANEOUS ITEMS.
5. SHEET A-2.2; FLOOR PLAN: A NOTE IN HALL 141 INDICATES "DASHED LINE INDICATES SHELFING PER REPORT". WHAT REPORT IS THIS, AND WHERE IS IT? VERIFY AND PROVIDE.
6. SHEET A-2.2; FLOOR PLAN: ARE ALL OF THE DOORS AND WALLS ON THIS PLAN NEW? VERIFY.
7. SHEET A-2.2 (FLOOR PLAN); SHEET A-7.0: BUILDING SECTION A/7.0 IS CUT ON THE PLAN FROM NORTH TO SOUTH, BUT SECTION A IS CUT FROM EAST TO WEST. VERIFY.
8. SHEET A-2.2 (FLOOR PLAN); SHEET A-7.0: BUILDING SECTION B/7.0 IS CUT ON THE PLAN, BUT IS NOT ON SHEET A-7.0. CLARIFY.
9. SHEET A-2.2; FLOOR PLAN KEYNOTES: NOT ALL OF THE KEYNOTES LISTED ARE ON THE PLAN. VERIFY.
10. SHEET A-2.4: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE MISCELLANEOUS ITEMS.
11. SHEET A-4.0; ELEVATION 29: THE SINK IN THE BREAK ROOM MUST MEET THE HEIGHT REQUIREMENTS (2'-10" MAXIMUM) OF THE ICC/ANSI A117.1-2003 SECTION 902, AND THE 2006 IBC SECTION 1109.3. VERIFY.
12. SHEET A-6.0; ELEVATION KEYNOTES: NOT ALL OF THE KEYNOTES LISTED ARE ON THE ELEVATIONS. VERIFY.
13. SHEET A-7.1; SECTION B: REMOVE THE KEYNOTES SHOWN ALONG GRID LINE E.
14. SHEET A-7.1; CONSTRUCTION KEYNOTES: NOT ALL OF THE KEYNOTES LISTED ARE ON THE SECTIONS. VERIFY.
15. SHEET A-9.0; DETAIL 5: THE TUCSON DEPARTMENT OF TRANSPORTATION REQUIRES 7'-0" TO THE BOTTOM OF THE RESERVED PARKING SIGN. REVISE AND ENLARGE DIMENSIONS.
16. SHEET S-2.1; FOUNDATION PLAN: PROVIDE A NORTH ARROW ON THE PLAN.
17. SHEET S-2.1; FOUNDATION PLAN: THE MASONRY WALL AND ITS FOOTING AT THE EQUIPMENT YARD WERE NOT FOUND IN THE STRUCTURAL CALCULATIONS.PROVIDE.
18. SHEET S-3.1 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEETS 4 AND 5): THE CALCULATIONS INDICATE A BEAM RB6 (SIM) AT ONE AREA, WHICH IS SHOWN TO BE A 3 1/8" X 15" BEAM AT THE TOWER, AND A 5 1/8" X 12" BEAM AT THE SLOPED ROOFS. THE FRAMING PLAN INDICATES A B3 (3 1/8' X 10 1/2" GLB) LOW BEAM, AND A B4 (W8X28 STEEL BEAM) HIGH BEAM. COORDINATE.
19. SHEET S-3.1; FRAMING PLAN: PROVIDE A NORTH ARROW ON THE PLAN.
20: GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/24/2012 KEN BROUILLETTE FIRE REVIEW Approved
07/27/2012 ROBERT SHERRY WATER REVIEW Approved
07/30/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied If domestic cold water is to be used for emergency cooling, revise the drain (currently 3") to avoid overloading. Reference: Section 710.5, UPC 2006.
07/30/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Specify the acceptable piping and, as appropriate, insulation materials to be used for the chilled water, steam, steam condensate, humidifier and duct drains, and the A/C condensate drainage. Reference: Section 106.3.1, IMC 2006.
2. Clarify the note on detail 3/M3.2 calling for an "air cushion on top of the storage tank". Is this a component of the listed chiller or a non-diaphragm expansion tank? Reference: Section 1205.1.6, IMC 2006.
3. Show the location of the cryogen vent on the roof along with the indication of the danger area around the vent. Reference: Section 304.1, IMC 2006.
4. Revise the steam piping shown in detail 3/M3.2 to correspond to the manufacturer's requirements for slopes and condensate traps for both the steam and the condensate being drained back to the humidifier. Reference: Section 304.1, IMC 2006.
5. Provide calculations to show that the use of domestic cold water for equipment cooling complies with the requirements of Section 1201.3, IMC 2006, as amended by the City of Tucson.
08/03/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM04045
5515 E th ST
Int and Ext Remodel Medical

1. Provide a fault current analysis, from utility on through to electrical equipment.
2. Cannot locate Panel AC on plans,
3. Sheet E-0,indicates existing outside lights and monument sign not part of this contract,however the circuits feeding them sare to be reconnect to new panel LV ? Does this mean the outdoor lighting is to remain the same and just reconnected ? Also the ODLC compliance report makes reference to Table 5.1, the new ODLC is in use and the Table is now under Chapter 401, and the output lumens has changed.

Ray T Majuta
Elect Pln Review
PDSD, City of Tucson,
8/7/2012
Ray.Majuta@tucsonaz.gov
08/08/2012 GERRY KOZIOL WWM REVIEW Approved