Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM03975
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/27/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide structural calculations for the roof framing and foundation designs. 2. If the shell space is to be a true shell space, refrigerators, cabinets and sinks would not be installed. Please eliminate these finish items or call out "Not in this Contract, for Future Installation". 3. The water closet in the women's toilet room is not accessible. Please comply with space requirements of ICC A117.1, Section 604.3. No other fixture may be within the required clearance space. END OF REVIEW |
| 09/05/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: SKYLINE PEDIATRICS, P.C. - DP12-0094 2: CONNECTING TO EXISTING 8" PUBLIC SEWER WITH 4" HCS- CONNECTION TO 1" C.W. 3: NEED APPROVED WATER PLAN SHOWING LOCATION AND SIZE OF WATER METER FOR THIS NEW COMMERCIAL BUILDING FOR CALCULATION OF WASTWATER CONNECTIN FEES - VACANT LOT - NO PREVIOUS BUILDING - NEED WATER METER UPSIZING FORM FROM WATER SUPPLIER 4: DP PLAN APPROVED PER PCRWRD/CHAD AMATEAU 9/5/12 5: NEED PIMA COUNTY ADDRESSING REVIEW - MICHELENE NOWAK- 740-6480- BUILDING INCUDES ANOTHER SUITE |
| 09/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/10/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/11/2012 | TERRY STEVENS | ZONING | REVIEW | Denied | Zoning cannot approve until the development package has been approved. |