03/01/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03959
1. Provide the size of conductors and conduit feeding G-1 fron Panel G.
2. Panel G rated 14,000 aic, Panel G-1 rated 10,000 aic,
why ?
3. Panel G-1 does not appear to have clearance required per 110.26 NEC required on sheet E2.0A.
4. Circuit 1,3 Panel G-1, cannot locate on plan.

Ray T Majuta
PDSD, C of Tuc
Elect Plan Review
3/1/2013