Permit Number: T12CM03959
Parcel: 140420740

Address:
7150 S TUCSON BL

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM03959
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03959
1. Provide the size of conductors and conduit feeding G-1 fron Panel G.
2. Panel G rated 14,000 aic, Panel G-1 rated 10,000 aic,
why ?
3. Panel G-1 does not appear to have clearance required per 110.26 NEC required on sheet E2.0A.
4. Circuit 1,3 Panel G-1, cannot locate on plan.

Ray T Majuta
PDSD, C of Tuc
Elect Plan Review
3/1/2013
03/01/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/01/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/07/2013 SHANAE POWELL APPROVAL SHELF Completed
03/07/2013 SHANAE POWELL OUT TO CUSTOMER Completed