Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM03959
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/01/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03959 1. Provide the size of conductors and conduit feeding G-1 fron Panel G. 2. Panel G rated 14,000 aic, Panel G-1 rated 10,000 aic, why ? 3. Panel G-1 does not appear to have clearance required per 110.26 NEC required on sheet E2.0A. 4. Circuit 1,3 Panel G-1, cannot locate on plan. Ray T Majuta PDSD, C of Tuc Elect Plan Review 3/1/2013 |
03/01/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
03/01/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved |