Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide complete structural calculations.
2. Send a letter to the building official, Mr. Ron Boose, listing the wood trusses as a deferred submittal.
SHEET A3
3. The new toilet room is not accessible. Reference ICC A117.1, Chapter 6.
4. Door "Y" is non compliant. Rference ICC A117.1, Section 4042.3.1, Door Clearances.
5. Show accessible portion of Reception Counter as required by ICC A117.1, section 904.
END OF REVIEW
07/26/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; the specified water heater (Eemax model SP3512) is not capable of limiting the water temperature to 110 degrees Fahrenheit. [Original comment: Show how the hot water temperature at the lavatory is to be limited to 110 degrees Fahrenheit. Reference: Section 416.1, IPC 2006.]
07/30/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03933

Provide a grounding system for the new service.

Ray T Majuta
Elect Pln Review
PDSD, C of Tuc
7/30/2012
Ray@Majutatucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed