Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03933
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide complete structural calculations. 2. Send a letter to the building official, Mr. Ron Boose, listing the wood trusses as a deferred submittal. SHEET A3 3. The new toilet room is not accessible. Reference ICC A117.1, Chapter 6. 4. Door "Y" is non compliant. Rference ICC A117.1, Section 4042.3.1, Door Clearances. 5. Show accessible portion of Reception Counter as required by ICC A117.1, section 904. END OF REVIEW |
| 07/26/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; the specified water heater (Eemax model SP3512) is not capable of limiting the water temperature to 110 degrees Fahrenheit. [Original comment: Show how the hot water temperature at the lavatory is to be limited to 110 degrees Fahrenheit. Reference: Section 416.1, IPC 2006.] |
| 07/30/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03933 Provide a grounding system for the new service. Ray T Majuta Elect Pln Review PDSD, C of Tuc 7/30/2012 Ray@Majutatucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/23/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |