Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03890
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/29/2012 | GERRY KOZIOL | WWM | REVIEW | Approved | |
07/10/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
07/12/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. COT minimum lettering size for all drawings is 3/32" actual size for all upper and lower case. Revise all sheets that are non-compliant and resubmit. SHEET A0 2. The existing building plan does no reflect the floor plan: a. North arrows differ b. The floor plan size and configuration is not the same. c. Show accurate floor plan on the Existing Building Plan to industry standard scale size and resubmit. SHEET A-1 3. Where are your water dispensers? 4. Where is your service sink? SHEET H1 5. At detail 1, all accessible mounting heights are to be as per ICC A117.1, Chapter 6. Please review and make all adjustments required. 6. All details must be drawn to an acceptable industry standard scale and the scale is to be noted in the title. Revise all details accordingly and resubmit. 7. Please provide large scale toilet elevations showing all accessibility requirements such as heights, accessories, fixtures, dimensions and clearances. 8. Detail 4 is non-compliant with ICC A117.1, Section 604.3, water closet clearances. 9. Detail 11 in non-compliant with ICC A117.1, Chapter 7 for accessible signage. 10. At detail 7 show maximum accessible parking grade slopes at 2% in all directions. 11. The height for detail 13 is to be as per COT DOT development standard of 7'-0". SHEET P1.1 12. Provide structural details and calculations for the water heater wall mounted bracket and also the supporting wall strength. END OF REVIEW |
07/19/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/19/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
07/20/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for business occupancy (e.g. a service sink and a drinking fountain). See also Section 1109.5.1, IBC 2006. 2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 106.3.1 and 301.2, IPC 2006. 3. Show how the temperature of the hot water supplied to the sinks and lavatories complies with the requirements of Section 504.3, IECC 2006. 4. Provide an approved anti-siphon device (e.g. vacuum relief valve) for storage-type water heaters located above any fixture outlets. Reference: Section 504.1, IPC 2006. 5. Provide a watertight pan of galvanized steel (minimum 24-gage) or other approved material under the water heater with a drain to an approved location. Reference: Section 504.7, IPC 2006. 6. Verify that the developed length of the hot water supply does not exceed 100-feet, which would lead to the requirement for a hot water recirculation system. Reference: Section 607.2, IPC 2006. 7. Show how the water connections to each of the dental chairs are protected from backflow. Reference: Section 608.2, IPC 2006. 8. Revise the size of the branch vents to comply with the requirements of Section 916.4.1, IPC 2006. |
07/25/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |