Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM03824
Parcel: 13405118R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03824
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2012 STEVE SHIELDS ZONING REVIEW Approved
06/27/2012 PAUL MACHADO ENGINEERING REVIEW Approved
06/27/2012 ERIC NEWCOMB ADA REVIEW Passed
06/27/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; DETAIL B: A VERTICAL GRAB BAR IS NOT INDICATED ON THIS DETAIL. PROVIDE.
2. SHEET A1.0 (DETAIL B); SHEET A3.0 (ELEVATION A): IF YOU WANT TO LEAVE BOTH OF THESE ON THE DRAWINGS, CORDINATE THE GRAB BAR LENGTHS AND LOCATIONS.
3. SHEET A3.0; ELEVATION A: LOCATE THE PAPER DISPENSER PER THE ICC/ANSI A117.1-2003, FIGURE 604.7.
4. GENERAL: COORDINATE THE RESTROOM ELEVATIONS WITH THE ICC/ANSI A117.1-2003, FIGURE 604.5.1.
06/27/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
06/28/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2006.
06/28/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
06/28/2012 ROBERT SHERRY WATER REVIEW Approved
06/28/2012 MARTIN BROWN FIRE REVIEW Approved
06/28/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03824
1020 S Harrison
Medical out patient

1. The electric water heaters nor the ricir pump not on electrical plan.
2. Verify the Medical Outpatient Facility will not have to comply with 2005 NEC 517 on Patient Care Areas or General Care Areas.

Ray T Majuta
Electrical Plan Review
PSDS
6/28/2012
C of Tuc
07/05/2012 CAGUILA1 WWM REVIEW Needs Review