Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; CODE ANALYSIS DATA: THE BUILDING CODE USED BY THE CITY OF TUCSON IS THE 2006 IBC. REVISE.
2. SHEET A1.0; CODE ANALYSIS DATA: PROVIDE THE SQUARE FOOTAGE OF THE PROJECT CONDO.
3. SHEET A2.1; SECOND FLOOR PLAN: PROVIDE STRUCTURAL CALCULATIONS FOR THE NEW FLOOR JOISTS, COLUMN, AND WALLS.
4. GENERAL: PROVIDE A VALUATION FOR THE LABOR AND MATERIALS OF THE NEW WORK.
06/27/2012 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
06/27/2012 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/27/2012 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review