Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM03729
Parcel: 13015001A

Address:
4646 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03729
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; FLOOR PLAN KEYNOTES: NOTE 11 WAS NOT FOUND ON THE DRAWINGS. VERIFY.
2. SHEET A4.0; ELEVATION KEYNOTES: NOTE 3 WAS NOT FOUND ON THE ELEVATIONS. VERIFY.
3. SHEET A7.1; DETAIL 2: SHOULD THE DOWEL INTO THE EXISTING FOOTING BE EPOXIED? VERIFY.
4. SHEET A7.2; PLAN 1: THE SERVICE DESK HEIGHT SHALL MEET THE ACCESSIBILITY REQUIREMENTS OF THE IBC SECTION 1109.12.3 AND THE ICC/ANSI CHAPTER 9. VERIFY.
5. SHEET A7.2; PLAN 2: THE SERVICE DESK HEIGHT SHALL MEET THE ACCESSIBILITY REQUIREMENTS OF THE IBC SECTION 1109.12.3 AND THE ICC/ANSI CHAPTER 9. VERIFY.
6. SHEET S2.1; FOUNDATION PLAN: SINCE THE STEEL COLUMNS ARE NOTED ON THIS PLAN, EITHER HAVE THE COLUMN SCHEDULE ON THIS SHEET, OR REFERENCE SHEET S3.1 FOR THAT SCHEDULE.
7. SHEET S2.1; FOUNDATION PLAN NOTES: NOTE 4 WAS NOT FOUND ON THE PLAN. VERIFY.
8. SHEET S2.1; FOUNDATION PLAN: IN THE NORTHWEST CORNER, THERE IS A PLAN NOTE 5 INDICATED, BUT THERE IS NO 5 IN THE PLAN NOTES. VERIFY.
9. SHEET S3.1; FRAMING PLAN: WHY IS THE DETAIL 111 NOT NOTED AS A 200 DETAIL? ALL DETAILS FOR THE ROOF FRAMING ARE 200 SERIES. VERIFY.
10. SHEET S3.1 (FRAMING PLAN); SHEET S5.1 (DETAILS 201 AND 202): CLARIFY ON THE PLAN OR ON THE DETAILS WHICH DETAIL REFERENCES THE EAST SIDE, AND WHICH REFERENCES THE WEST SIDE.
11. SHEET S4.1; DETAIL 101: CHANGE NOTE 2 ON THE KEYED JOINT DETAIL.
12. SHEET S4.1; DETAIL 107: NOTE 6 WAS NOT FOUND ON THE DETAIL. VERIFY.
13. SHEET S4.1; DETAIL 111: THE NOTES DO NOT MATCH THE CALL-OUTS ON THE DETAIL. COORDINATE.
14. SHEET S5.1; DETAIL 206: CHECK THE VERBIAGE IN NOTES 2 AND 3.
15. SHEET S5.1; DETAIL 211: NOTE 2 WAS NOT FOUND ON THE DETAIL. VERIFY.
16. SHEET S5.1; DETAIL 211: CHECK THE VERBIAGE IN NOTES 3 AND 4.
17. SHEET S5.1; DETAIL 212: CHECK THE VERBIAGE IN ALL OF THE NOTES.
18. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED IN WRITING BY RON BOOSE (BUILDING OFFICIAL) BEFORE THOSE SUBMITTALS WILL BE REVIEWED. RON.BOOSE@TUCSONAZ.GOV.
19. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/19/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/25/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/25/2012 ROBERT SHERRY WATER REVIEW Approved
07/26/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006.
2. Clarify the mechanical energy compliance certificate; the title information indicates that the building is located in Denton, Texas.
07/30/2012 GERRY KOZIOL WWM REVIEW Passed