Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM03718
Parcel: 134090220

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM03718
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: QT #1476 - 8530 E. Broadway Blvd.
T12CM03718, T12CM03718 & T12BU00792
Building Plan (1st Review)

TRANSMITTAL DATE: June 25, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/29/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide the canopy total square footage for pricing and fee purposes.
2. Please provide approved site plan.
3. For the men's room 106, details A6/503, A1/A213 and D1/A213: please relocate the accessible urinal to the center urinal to comply with ICC A117.1, Sections 606 and 305.7.
4. The special inspector's Certification needs the actual name of the inspector that is to conduct the inspection, not the name of the company. Please revise form accordingly and resubmit.
5. Please provide a letter to the building official, Mr. Ron Boose, stating that the steel trusses are to be deferred for a later review.
END OF REVIEW
07/03/2012 KEN BROUILLETTE FIRE REVIEW Approved
07/05/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the plumbing code to be used for this activity. The Code analysis on sheet N101 refers to the 2006 UPC but on several plumbing sheets, reference is made to a combination waste and vent system using criteria from Section 912 of the 2006 IPC (no combination waste and vent system was found on the drawings however). This review has been made using the 2006 UPC.
2. Appliances (e.g. smoothie machines, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
3. Revise the water pressure calculations to include the pressure drop due to the second reduced pressure backflow preventer for the domestic water service located in Room 110. The civil drawings show the installation of a reduced pressure backflow preventer assembly by the water meter, as required by Tucson Water. Reference: Section 610.2, UPC 2006. See also: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
4. The rim elevation of the next upstream sanitary manhole (2655.18') is higher than the first floor elevation (2653.50'). Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
5. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area.
6. Provide protection of the trap seals for all floor drains subject to infrequent use. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson.
7. Provide the specifications for the gravity grease interceptor and show that the size of the interceptor complies with Section 1014.3.6, UPC 2006. (Note: specifications, installation and size of the gravity grease interceptor are not adequately shown on the civil drawings.)
8. Coordinate the layout of the roof drains and overflow roof drains serving the main roof with the architectural roof plan on sheet A130. (Note that what appears to be scuppers and overflow scuppers along the south wall of the building on sheet P104 are identified as light fixtures on the architectural plans.) Reference: Sections 103.2.3 and 1101.11.1, UPC 2006.
9. Provide a cleanout at the base of each roof drain leader from the low canopies prior to their connection with the horizontal storm drain. Reference: Section 1101.12.2, UPC 2006.
10. Revise the orientation of the storm drain cleanouts located at the northeast, northwest, southwest, and southeast corners of the building (e.g. see sheet C120) so that they open to allow cleaning in the direction of flow. Reference: Sections719.4 and 1101.12.1, UPC 2006.
07/05/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/05/2012 ROBERT SHERRY WATER REVIEW Approved
07/16/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03718
8530 E Broadway
Quick Trip

1.Sheet E001, concerning the location of the Emergency Fuel Shut Off Switch, per NEC 2005 514.11, it requires the switch to be located remote from the dispensers not near the dispenders in order that a person operating the switch is away from any hazards.
2. Sheet E106, the Outdoor Lighting Calculation is showing an allowance of 300,000 lumens for Area E3 per acre, please correct to show 250,000 lumens per acre, which comes from the 2012, Tucson Outdoor Code Ord # 10963.
3.Sheet E107 shows the Signlighter Straight Arm Fixture used for outdoor and indoor, will this fixture be used indoors or outdoors ? If outdoor use,does not comply with a full cutoff fixture, it would have to be listed under unshielded fixture and listed under Unshielded Lighting and calculated under another Option, see new Tucson Outdoor Ord # 10963.

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
7/17/2012
Ray.Majuta@tucsonaz.gov
07/19/2012 LOREN MAKUS ENGINEERING REVIEW Approved
07/23/2012 GERRY KOZIOL WWM REVIEW Denied 1. QUICK TRIP #1476
2. CONNECTIONG TO EXISTING ON SITE PRIVATE SEWER PER APPROVED DP PER PCRWRD/TOM PORTER 07/19/12
3. NED WASTEWATER IWC REVIEW & APPROVAL OF GREASE INTERCEPTOR TOM TOMCHAK 724-6200 3035 W EL CAMINO DEL CERRO
4. CONNECTION TO NEW 2" WATER METER - NEEDS TO SUBMIT INFORMATION FOR UPSIZING OR RELOCATION OF EXISTING WATER METERS FOR CREDIT IF APPLICABLE

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2012 CPIERCE1 APPROVAL SHELF Completed
08/10/2012 CPIERCE1 OUT TO CUSTOMER Completed
08/10/2012 CPIERCE1 REJECT SHELF Completed