Permit Number: T12CM03684
Parcel: 115044910

Review Status: Completed

Review Details: OTHER

Permit Number - T12CM03684
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03684
1020 N Tyndall
Construction Power

1. Provide a fault current summary
2. Size conduit and conductors to and from 75kav and 45 kva transformers.
3.If Series Rated System to be used on fault current break down provide information with it
4. Provide fault current levels panels are to be rated
5. Identy fuses types to be used.
6. Specify all equipment to be used outdoors to be NEMA rated N-3

Ray T Majuta
Electricval Plan Review
PDSD City of Tucson
6/21/2012
Ray,Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/22/2012 CPIERCE1 OUT TO CUSTOMER Completed