Permit Number - T12CM03684
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03684 1020 N Tyndall Construction Power 1. Provide a fault current summary 2. Size conduit and conductors to and from 75kav and 45 kva transformers. 3.If Series Rated System to be used on fault current break down provide information with it 4. Provide fault current levels panels are to be rated 5. Identy fuses types to be used. 6. Specify all equipment to be used outdoors to be NEMA rated N-3 Ray T Majuta Electricval Plan Review PDSD City of Tucson 6/21/2012 Ray,Majuta@tucsonaz.gov |