Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM03657
Parcel: 99999999A

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T12CM03657
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/10/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Provide a return grille in the massage room. Reference: Tucson Code, Chapter 7, Article VVII, Section 7-137.
05/10/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the drain piping for the floor drains as shown on the plumbing plan in rooms 121 and 123 to coordinate with the sanitary riser. [Initial comment: Coordinate the plumbing riser diagrams with the revised plumbing plans. Reference: Section 106.3.1, IPC 2006.]
2. Comment not addressed. Provide the revised civil drawing to coordinate with the revised plumbing plans. Reference: Section 106.3.1, IPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/17/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed