Permit Number: T12CM03657
Parcel: 99999999A

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T12CM03657
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03657

1. Provide fault current calculations for new 3 phase service and indicate if individual panels are to require fully rated breakers for panels according to thier fault current ratings.
2. City of Tucson Submittal Requirements indicate phases for panels to be with 15% of each other.
3. Indicate at individual sub-panels which phases are to be used, since main panel is 3 phase and all sub panels single phase.
4. The lighting circuits revised on Sheet E101L need to be renamed in the panel schedules.

Ray Majuta
DSD, Tucson,
Elect Plan Review
4/3/2013
Ray.Majuta@tucsonaz.gov
04/03/2013 MARTIN BROWN FIRE REVIEW Approved
04/03/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a return grille in the massage room. Reference: Tucson Code, Chapter 7, Article VVII, Section 7-137.
04/03/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/03/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing riser diagrams with the revised plumbing plans. Reference: Section 106.3.1, IPC 2006.
2. Provide the revised civil drawing to coordinate with the revised plumbing plans. Reference: Section 106.3.1, IPC 2006.
3. Verify the locations of the water meter and the reduced pressure backflow prevention assembly. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf

Final Status

Task End Date Reviewer's Name Type of Review Description
04/05/2013 CPIERCE1 APPROVAL SHELF Completed
04/05/2013 CPIERCE1 OUT TO CUSTOMER Completed