Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 4TH
Permit Number - T12CM03657
Review Name: REVISION - - 4TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/03/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03657 1. Provide fault current calculations for new 3 phase service and indicate if individual panels are to require fully rated breakers for panels according to thier fault current ratings. 2. City of Tucson Submittal Requirements indicate phases for panels to be with 15% of each other. 3. Indicate at individual sub-panels which phases are to be used, since main panel is 3 phase and all sub panels single phase. 4. The lighting circuits revised on Sheet E101L need to be renamed in the panel schedules. Ray Majuta DSD, Tucson, Elect Plan Review 4/3/2013 Ray.Majuta@tucsonaz.gov |
| 04/03/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/03/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a return grille in the massage room. Reference: Tucson Code, Chapter 7, Article VVII, Section 7-137. |
| 04/03/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/03/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the plumbing riser diagrams with the revised plumbing plans. Reference: Section 106.3.1, IPC 2006. 2. Provide the revised civil drawing to coordinate with the revised plumbing plans. Reference: Section 106.3.1, IPC 2006. 3. Verify the locations of the water meter and the reduced pressure backflow prevention assembly. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/05/2013 | CPIERCE1 | APPROVAL SHELF | Completed |
| 04/05/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |