Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 4TH
Permit Number - T12CM03655
Review Name: REVISION - - 4TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/20/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the waste & vent riser diagram (2/P103) with the revised plumbing plan. 2. Show the connection of the 4"FD to the building drain. |
| 05/20/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A101: PROVIDE A REGISTERED PROFESSIONAL LICENSE, SIGNATURE, AND EXPIRATION DATE ON THIS SHEET. 2. SHEET A101: IT APPEARS SOME OPENINGS HAVE BEEN FILLED IN, AND OTHER NEW OPENINGS HAVE BEEN ADDED. PROVIDE THOSE ON THESE DRAWINGS, AND INDICATE DETAILS, HEADERS, ETC. FOR THEM. |
| 05/21/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | PROVIDE HMIS FOR STORAGE |
| 05/21/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/30/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |