Permit Number: T12CM03655
Parcel: 99999999A

Address:
1000 E 22ND ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM03655
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied A demand flow of 29 GPM (from the Domestic Water Entrance detail) through a 3/4" water meter and a ¾" water service pipe results in an excessive pressure drop and a velocity greater than the maximum 8 FPS allowed for either plastic or copper piping. In addition, Tucson Water limits the 3/4" meter to a maximum demand of 22.5 GPM. Reference: Table 604.4 (c), IPC 2006, as amended by the City of Tucson.
12/10/2012 SPOWELL1 WWM REVIEW Needs Review