Permit Number: T12CM03619
Parcel: 99999999A

Review Status: Completed

Review Details: OTHER

Permit Number - T12CM03619
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The building sewers for buildings 2, 5, 7, 8, 9, 10, 11, 12, 13, and 14 have been changed from 6" to 4". A maximum of 180 drainage fixture units may be connected to a 4" building sewer at a slope of less than 2%; these buildings have 189 drainage fixture units. Reference: Section 710.1, IPC 2006.
2. The size of the building sewers for buildings 3, 4, 6, and the maintenance building are not indicated on the drawings. Reference: Section 107.2.1, IBC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed