Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T12CM03619
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The building sewers for buildings 2, 5, 7, 8, 9, 10, 11, 12, 13, and 14 have been changed from 6" to 4". A maximum of 180 drainage fixture units may be connected to a 4" building sewer at a slope of less than 2%; these buildings have 189 drainage fixture units. Reference: Section 710.1, IPC 2006. 2. The size of the building sewers for buildings 3, 4, 6, and the maintenance building are not indicated on the drawings. Reference: Section 107.2.1, IBC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/27/2014 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |