Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM03602
Parcel: 124050600

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03602
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2012 STEVE SHIELDS ZONING REVIEW Approved
06/19/2012 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
06/19/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03602
944 E University Bl

1. Must provide a fixture schedule showing, wattage of lamps,number of lamps per fixture,voltage.
2. Provide 2006 IECC Lighting Budget Summary for job.

Ray T Majuta
Electrical Plan Check
6/19/2011
06/19/2012 LHANLY1 WATER REVIEW Passed
06/19/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T1 (CODE REVIEW); SHEET A1 (FLOOR PLANS): THE SQUARE FOOTAGE INDICATED ON T1 FOR BOTH LEVELS DIFFERS FROM THE SQUARE FOOTAGE SHOWN ON SHEET A1. REVISE.
2. SHEET T1 (CODE REVIEW); SHEET A1 (FLOOR PLANS): THE OCCUPANT LOAD INDICATED ON T1 FOR BOTH LEVELS DIFFERS FROM THE OCCUPANT LOADS SHOWN ON A1. REVISE.
3. SHEET A1; DETAIL 1: THE DETAIL INDICATES THIS DETAIL IS FOR FIRST TO SECOND FLOOR. PROVIDE A DETAIL FOR SECOND FLOOR TO ROOF.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/19/2012 LHANLY1 WWM REVIEW Passed
06/19/2012 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed
06/19/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
06/19/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/19/2012 LEERAY HANLY ADA REVIEW Passed
06/20/2012 MARTIN BROWN FIRE REVIEW Approved