Review Details: COMMERCIAL - TI
Permit Number - T12CM03600
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/19/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 06/19/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/19/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/19/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 06/19/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/20/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/20/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. 2. Show the balancing information for the existing relocated diffusers. Reference: Sections 106.3.1 and 403.3.4, IMC 2006. |
| 06/20/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the plumbing schedule, plans, and riser diagrams. Reference: Section 106.3.1, IPC 2006. 2. Provide specifications and listing information for the existing "Insta-hot"; show that it is listed to serve two lavatories. Reference: Sections 303, 501.5, 501.6, and 501.8, IPC 2006 and Section 504.3, IECC 2006. 3. Clarify the trap priming valve shown in the supply diagram; what fixture is it serving? Reference: Section 106.3.1, IPC 2006. 4. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). |
| 06/21/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/21/2012 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 06/21/2012 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved |