Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03500
4821 E Grant RD

1. Now that the lumen output per fixture has been provided
(2400 for each) the installation does not comply with 2012
City of Tucson Outdoor Ord # 10963, 102..4.2, which requires each additional full cut of fixture to be limited to 2000 lumens.

Ray T Majuta
PDSD, C of Tuc
Electrical Plan Review
10/04/2012