Permit Number: T12CM03500
Parcel: 110113670

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM03500
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. The revised vents for the non-handicapped water closet in the women's restroom and the revised floor drain (for equipment #71A and 72A) appear to have horizontal vents. [Original comment: Each vent pipe shall rise vertically to a minimum of 6" above the flood-level rim of the fixture it serves before connecting to any other vent (e.g. the gravity grease interceptor). Reference: Section 905.3, UPC 2006.]
08/13/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03500

1. Last review item #1 requested 2006 IECC Lighting Budget Report. Went through all Electrical Sheets and submitted material, no IECC Report.

Ray Majuta
Elect Pln Review
PDSD, C of Tucson
8/13/2012
Ray.Majuta@tucsonaz.gov
08/13/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. The supply air is being introduced into the restrooms continuously during the hours of operation; show that the exhaust fans will be operating continuously during the hours of operation also. [Original comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.]
08/15/2012 CAGUILA1 WWM REVIEW Needs Review
08/15/2012 CAGUILA1 ZONING REVIEW Needs Review