Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM03500
Parcel: 110113670

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03500
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2012 JASON GREEN ENGINEERING REVIEW Approved Building plan will be stamped for final approval once the DP Package DP12-0090 has been approved.
06/25/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/25/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A2
1. Door 01 does not have the accessible clearance as required by ICC ANSI 117.1, Section 404.2.3.1; 4'-6" wide with a closer.
SHEET A4.1
2. At detail 10:
a. The Urnial must be 3'-0" wide with stall deeper than 24". Reference sections 305 and 605, specificly section 305.7.
b. In the women's toilet, the waste dispenser is encroaching into the required 5' diameter turning radius.
SHEET S1.0
3. Please provide Special Inspector's Certification as scheduled.
END OF REVIEW
06/27/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve the building plans until the development package has been approved.
06/28/2012 ROBERT SHERRY WATER REVIEW Approved
06/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Verify that the location of the reduced pressure backflow preventer that will serve the future misting system conforms to the access and clearance requirements of Section 603.3.4, UPC 2006.
2. The branch piping sizes called out for the water closet and urinal flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
3. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length. Reference: Section 707.4, UPC 2006.
4. Verify that the floor cleanouts are readily accessible and have adequate clearance. Reference: Sections 203.0 and 707.9, UPC 2006.
5. Each vent pipe shall rise vertically to a minimum of 6" above the flood-level rim of the fixture it serves before connecting to any other vent (e.g. the gravity grease interceptor). Reference: Section 905.3, UPC 2006.
06/29/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
07/10/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03500
4821 E Grant Rd
Paridise Bakery and Cafe

The Electrical Plans have been denied for the following, address each and indicate how each was addressed.
1. Provise 2006 IECC Lighting Budget Compliance report,
ComCheck ok. Indicate which switching requirements to be met per IECC.
2. Relocate fixture panel schedule to electrical sheets, preferably lighting sheet or after.
3. Sheet E3.1, Circuit LP-12 shown as load, as spare in panel.
4. Sheet E5.1, provide calculation showing how you arrived
on demand load of 483.4 amps for panel M. Show demands added.
5. Provide a location for CT enclosure and 800 Amp Main Disconnect.
6. Show on Sheet E5.1, the conductors(number of),conduit sizes for the following:
1. conductors from Utility to CT enclosure
2. conductors from 800 Amp Main Disconnect to
Panel M.
7. Indicate the type of fuse to be used in the 800 Amp
disconnect.
8. Indicate type of system ground for service to be used
and size.

Ray T Majuta
Electrical Plan Review
PDSD, City of Tucson
7/10/2012
Ray.Majuta@tucsonaz.gov
07/12/2012 GERRY KOZIOL WWM REVIEW Denied 1. PARADISE BAKERY & CAFE
2. CONNECTING TO EXISTING ON - SITE PRIVATE SEWER
3. NEED WASTEWATER / IWC REVIEW & APPROVAL OF GREASE INTERCEPTOR & PLUMBING FIXTURES CONNECTED TO IT - TOM TOMCHAK 724-6200 3035 W EL CAMINO DEL CERRO
4. NEED WATER METER CLARIFICATION FOR EXISTING BUILDING CONNECTING TO 2" WATER METER TO BE PROVIDED BY LANDLORD PER DOMESTIC WATER PLUMBING DRAWING P-2.4 - NOTE #4
5. NEED CAPCITY REVIEW & APPROVAL - PCRWRD / KURT STEMM 3RD FLOOR 740-6534