Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM03500
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/21/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | Building plan will be stamped for final approval once the DP Package DP12-0090 has been approved. |
06/25/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/25/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET A2 1. Door 01 does not have the accessible clearance as required by ICC ANSI 117.1, Section 404.2.3.1; 4'-6" wide with a closer. SHEET A4.1 2. At detail 10: a. The Urnial must be 3'-0" wide with stall deeper than 24". Reference sections 305 and 605, specificly section 305.7. b. In the women's toilet, the waste dispenser is encroaching into the required 5' diameter turning radius. SHEET S1.0 3. Please provide Special Inspector's Certification as scheduled. END OF REVIEW |
06/27/2012 | TERRY STEVENS | ZONING | REVIEW | Denied | Zoning cannot approve the building plans until the development package has been approved. |
06/28/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/29/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Verify that the location of the reduced pressure backflow preventer that will serve the future misting system conforms to the access and clearance requirements of Section 603.3.4, UPC 2006. 2. The branch piping sizes called out for the water closet and urinal flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 3. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length. Reference: Section 707.4, UPC 2006. 4. Verify that the floor cleanouts are readily accessible and have adequate clearance. Reference: Sections 203.0 and 707.9, UPC 2006. 5. Each vent pipe shall rise vertically to a minimum of 6" above the flood-level rim of the fixture it serves before connecting to any other vent (e.g. the gravity grease interceptor). Reference: Section 905.3, UPC 2006. |
06/29/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
07/10/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM03500 4821 E Grant Rd Paridise Bakery and Cafe The Electrical Plans have been denied for the following, address each and indicate how each was addressed. 1. Provise 2006 IECC Lighting Budget Compliance report, ComCheck ok. Indicate which switching requirements to be met per IECC. 2. Relocate fixture panel schedule to electrical sheets, preferably lighting sheet or after. 3. Sheet E3.1, Circuit LP-12 shown as load, as spare in panel. 4. Sheet E5.1, provide calculation showing how you arrived on demand load of 483.4 amps for panel M. Show demands added. 5. Provide a location for CT enclosure and 800 Amp Main Disconnect. 6. Show on Sheet E5.1, the conductors(number of),conduit sizes for the following: 1. conductors from Utility to CT enclosure 2. conductors from 800 Amp Main Disconnect to Panel M. 7. Indicate the type of fuse to be used in the 800 Amp disconnect. 8. Indicate type of system ground for service to be used and size. Ray T Majuta Electrical Plan Review PDSD, City of Tucson 7/10/2012 Ray.Majuta@tucsonaz.gov |
07/12/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. PARADISE BAKERY & CAFE 2. CONNECTING TO EXISTING ON - SITE PRIVATE SEWER 3. NEED WASTEWATER / IWC REVIEW & APPROVAL OF GREASE INTERCEPTOR & PLUMBING FIXTURES CONNECTED TO IT - TOM TOMCHAK 724-6200 3035 W EL CAMINO DEL CERRO 4. NEED WATER METER CLARIFICATION FOR EXISTING BUILDING CONNECTING TO 2" WATER METER TO BE PROVIDED BY LANDLORD PER DOMESTIC WATER PLUMBING DRAWING P-2.4 - NOTE #4 5. NEED CAPCITY REVIEW & APPROVAL - PCRWRD / KURT STEMM 3RD FLOOR 740-6534 |