Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment still not resolved; the electrical drawings still show the exhaust fan for the men's restroom switched with the lights. Revise the sequence of operation for the restroom exhaust fan in the men's restroom so that all of the air supplied to the restroom will be exhausted (i.e. exhaust shall continue even if the lights are off). Reference: Section 403.2.1 (4), IMC 2006.
08/10/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved