Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM03499
Parcel: 137055270

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM03499
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment still not resolved; the electrical drawings still show the exhaust fan for the men's restroom switched with the lights. Revise the sequence of operation for the restroom exhaust fan in the men's restroom so that all of the air supplied to the restroom will be exhausted (i.e. exhaust shall continue even if the lights are off). Reference: Section 403.2.1 (4), IMC 2006.
08/10/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved