Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM03499
Parcel: 137055270

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03499
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/06/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the sequence of operation for the restroom exhaust fan in the men's restroom so that all of the air supplied to the restroom will be exhausted (i.e. exhaust shall continue even if the lights are off). Reference: Section 403.2.1 (4), IMC 2006.
2. Comment not addressed. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
07/13/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03499
5169 S Santa Cruz
TI OLD NAVY

The electrical plans have been denied for the following, address each item and indicate how each was addressed. All items per 2005 NEC
1. Provide a fault current analysis, beginning at utility on through to panels.Indicate how fault current levels to be brought to safe level as per 110.9 ,10 and 110.22. Add this to Sheet E9-0.
2. Indicate on Sheet E1.0 the location of Main Service Disconnect.
3. Provide a Budget Lighting analysis per 2006 IECC, and indicate switching methods to be used.
4. Sheet E9-0, Equipment Schedule, roll up door listed as 460 volts 3 phase ?

Ray T Majuta
Electrical Plan Review
PDSD, City of Tucson
7/16/2012
Ray.Majuta@tucsonaz.gov